MNS低壓抽屜柜能靠墻安裝嗎?

發(fā)布時(shí)間:2021-01-15 來源:http://www.thx0451.com/ 瀏覽量:

關(guān)于低壓抽屜柜安裝規(guī)范,我國是統(tǒng)一規(guī)定的。根據(jù)變電所低壓配電室的配電設(shè)備布置,應(yīng)符合我國標(biāo)準(zhǔn)《10kV及以下變電所設(shè)計(jì)規(guī)范》(GB50053-94)的規(guī)定。關(guān)于低壓抽屜柜能否靠墻安裝,里面有明確的規(guī)定。敲黑板,劃,不能!不能!不能!重要的事情說三遍。
The installation specification of low-voltage drawer cabinet is unified by the state. According to the distribution equipment layout of the low-voltage distribution room of the substation, it should comply with the national standard "code for design of 10kV and below substations" (GB 50053-94). There are clear regulations about whether the low-voltage drawer cabinet can be installed against the wall. Knock on the blackboard, draw the point, no! No! No! Important things are to be repeated for 3 times.
雖然,有些低壓抽屜柜廠家說明中是可以靠墻安裝的,而且一部分低壓柜型號(hào)的產(chǎn)品,所有接線都是柜前操作,柜后面是封閉的,靠不靠墻似乎沒啥影響。但是考慮到巡視、檢修、通風(fēng)散熱考慮,開關(guān)柜與墻需要保持一定的距離。而且規(guī)定就是規(guī)定,在規(guī)定沒有更改之前,任何人不要有僥幸心理。萬一出了事故,違規(guī)安裝的責(zé)任誰也承擔(dān)不起。
Although, some low-voltage drawer cabinet manufacturers can be installed against the wall, and part of the low-voltage cabinet model products, all wiring is in front of the cabinet operation, the back of the cabinet is closed, it seems that there is no influence whether it is against the wall or not. However, considering the inspection, maintenance, ventilation and heat dissipation, the switch cabinet and the wall need to keep a certain distance. And the rule is the rule. Before the rule is changed, no one should take chances. In case of an accident, no one can bear the responsibility of illegal installation.
關(guān)于MNS低壓抽屜柜的安裝規(guī)范還有以下規(guī)定:
The installation specification of MNS low-voltage drawer cabinet also has the following provisions:
1·配電室的位置應(yīng)靠近用電負(fù)荷中心,設(shè)置在塵埃少、腐蝕介質(zhì)少、干燥和震動(dòng)輕微的地方,并宜適當(dāng)留有發(fā)展余地。
1. The distribution room should be located close to the power load center, where there is less dust, less corrosive medium, dry and slight vibration, and there should be room for development.
                            MNS低壓抽屜柜
2·配電設(shè)備的布置必須遵循、可靠、適用和經(jīng)濟(jì)等原則,并應(yīng)便于安裝、操作、搬運(yùn)、檢修、試驗(yàn)和監(jiān)測。
2. The layout of distribution equipment must follow the principles of safety, reliability, applicability and economy, and should be convenient for installation, operation, handling, maintenance, test and monitoring.
3·配電室內(nèi)除本室需用的管道外,不應(yīng)有其它的管道通過。室內(nèi)管道上不應(yīng)設(shè)置閥門和中間接頭;水汽管道與散熱器的連接應(yīng)采用焊接。配電屏的上方不應(yīng)敷設(shè)管道。
3. In the power distribution room, there should be no other pipes except the pipes needed in the room. Valve and intermediate joint shall not be set on indoor pipeline; the connection between water vapor pipeline and radiator shall be welded. No pipe shall be laid above the distribution panel.
4·落地式配電箱的底部宜抬高,室內(nèi)宜高出地面 50mm 以上,室外應(yīng)高出地面200mm 以上。底座周圍應(yīng)采取封閉措施,并應(yīng)能防止鼠、蛇類等小動(dòng)物進(jìn)入箱內(nèi)。
4. The bottom of floor type distribution box should be raised, indoor should be higher than the ground by more than 50 mm, outdoor should be higher than the ground by more than 200 mm. Sealing measures shall be taken around the base to prevent mice, snakes and other small animals from entering the box.
5·同一配電室內(nèi)并列的兩段母線,當(dāng)任一段母線有一級(jí)負(fù)荷時(shí),母線分段處應(yīng)設(shè)防火隔斷措施。
5. For two sections of bus in parallel in the same distribution room, when any section of bus has first-class load, fire isolation measures shall be set at the section of bus.
6·當(dāng)高壓及低壓配電設(shè)備設(shè)在同一室內(nèi)時(shí),且二者有一側(cè)柜頂有裸露的母線,二者之間的凈距不應(yīng)小于 2m。
6. When the high-voltage and low-voltage distribution equipment are located in the same room, and there is an exposed bus on one side of the cabinet top, the clear distance between the two should not be less than 2m.
7·成排布置的配電屏,其長度超過 6m 時(shí),屏后的通道應(yīng)設(shè)兩個(gè)出口,并宜布置在通道的兩端,當(dāng)兩出口之間的距離超過15m 時(shí),其間尚應(yīng)增加出口。
7. When the length of the distribution panel arranged in rows exceeds 6m, the channel behind the panel should be set with two outlets, which should be arranged at both ends of the channel. When the distance between the two outlets exceeds 15m, there should be more outlets between them.
8·成排布置的配電屏,其屏前和屏后的通道小寬度應(yīng)符合下表的規(guī)定。
8. The minimum width of the channel in front of and behind the distribution panel arranged in rows shall meet the requirements of the following table.