使用電氣設備或在電源周圍工作時,必須使用個體防護用品。如戴絕緣手套,穿保護性或絕緣性的圍裙及鞋。此外
電氣成套設備的零部件使用要怎么使用呢?
Personal protective equipment must be used when using electrical equipment or working around the power supply. For example, wear insulating gloves, protective or insulating aprons and shoes. In addition, how to use the parts of the complete electrical equipment safely?
配電柜柜內的電子元件的布置要盡量遠離主回路、開關電源及變壓器,不得直接放置或靠近柜內其他發熱元件的對流方向。
The electronic components in the distribution cabinet shall be arranged as far away from the main circuit, switching power supply and transformer as possible, and shall not be placed directly or close to the convection direction of other heating components in the cabinet.
主令操縱電器元件及整定電器元件的布置應避免由于偶然觸及其手柄、按鈕而誤動作或動作值變動的可能性,整定裝置一般在整定完成后應以雙螺母鎖緊并用紅漆漆封,以免移動。
The arrangement of the master control electrical components and the setting electrical components shall avoid the possibility of misoperation or action value change due to accidental touch of its handle and button. Generally, the setting device shall be locked with double nuts and sealed with red paint after setting to avoid movement.
系統或不同工作電壓電路的熔斷器應分開布置。
The fuses of the system or circuits with different working voltages shall be arranged separately.
熔斷器、使用中易于損壞、偶爾需要調整及復位的零件,應不經拆卸其他部件便可以接近,以便于更換及調整。
Fuses and parts that are easily damaged in use and occasionally need to be adjusted and reset shall be accessible without disassembling other parts for easy replacement and adjustment.
熔斷器安裝位置及相互間距離應便于熔體的更換。
The installation position and distance between fuses shall facilitate the replacement of the melt.
不同電壓等級的熔斷器要分開布置,不能交錯混合排列。
Fuses of different voltage levels shall be arranged separately and cannot be staggered and mixed.
有熔斷指示器的熔斷器,其指示器應裝在便于觀察的一側。
For fuse with fuse indicator, the indicator shall be installed on the side convenient for observation.
瓷質熔斷器在金屬底板上安裝時,其底座應墊軟絕緣襯墊。
When the porcelain fuse is installed on the metal base plate, its base shall be padded with soft insulation gasket.
低壓斷路器與熔斷器配合使用時,熔斷器應安裝在電源側。
When low-voltage circuit breaker and fuse are used together, the fuse shall be installed on the power supply side.
強弱電端子應分開布置;當有困難時,應有明顯標志并設空端子隔開或設加強絕緣的隔板。
Strong and weak current terminals shall be arranged separately; In case of difficulties, clear signs shall be provided and empty terminals shall be set for separation or partition with strengthened insulation shall be set.
In addition, the corresponding terminals shall have serial numbers, and the terminal strip shall be convenient for replacement and wiring; The height from the ground should be greater than 350 mm. Come to our website for more relevant content http://www.thx0451.com Ask!